Characteristics of Current Transformer MCQ || Characteristics of Current transformer Questions and Answers

41. The reluctance of the interleaved corner is ______ to the magnetizing current.

  1. Same
  2. Negative
  3. Inversely Proportional
  4. Directly Proportional

Answer.4. Directly Proportional

Explanation:

The stampings used for the laminations in current transformers must have high cross-sectional area than the ordinary transformers.

Due to this, the reluctance of the interleaved corners remains as low as possible. The reluctance of the interleaved corner is directly Proportional to the magnetizing current. Hence the corresponding magnetizing current is also small. The windings are placed very close to each other so as to reduce the leakage reactance. To avoid the corona effect, in a bar-type transformer, the external diameter of the tube is kept large.

 

42. For line voltages above 7 kV which current transformer is used?

  1. Oil Immersed
  2. Compound Filled
  3. Both 1 and 2
  4. Ring-type

Answer.3. Both 1 and 2

Explanation:

For small line voltages, tape and varnish are used for insulation. For line voltages above 7 kV, the oil-immersed or compound-filled current transformers are used.

For still higher voltages, i.e. 750 kV and above, porcelain bushings and oil-filled transformers are used.

 

43. To reduce the peak voltage between layers in the current transformer, the secondary winding is being ______

  1. Normalized
  2. Characterized
  3. Sectionalized
  4. Neutralized

Answer.3. Sectionalized

Explanation:

In current transformers, the windings are not placed on separate limbs as they are far apart. So there are large amounts of primary and secondary leakage fluxes.

To minimize these fluxes, the windings are sectionalized and interleaved. The sectionalized secondary winding also helps to reduce the peak voltage between layers in the current transformer.

 

44. A current transformer has a phase error of +5 degrees. The phase angle between the primary and secondary current is:

  1. 5 degree
  2. 95 degree
  3. 175 degree
  4. 85 degree

Answer.3. 175 degree

Explanation:

Given that,

Phase angle error θ = 5°

Phase angle between the primary current IP and secondary current IS  is given by

δ = 180° – θ

= 180° – 5°

175° 

 

45. Phase angle in a C.T. is defined as ______

a) \(\frac{180}{π} [\frac{I_m cosδ}{nI_s}]\) degrees

b) \(\frac{180}{π} [\frac{I_c sinδ}{nI_s}]\) degrees

c) \(\frac{180}{π} [\frac{I_m cosδ – I_c sinδ}{nI_s}]\) degrees

d) \(\frac{180}{π} [\frac{I_m sinδ – I_c cosδ}{nI_s}]\) degrees

Answer.c. \(\frac{180}{π} [\frac{I_m cosδ – I_c sinδ}{nI_s}]\) degrees

Explanation:

Phase angle error:

In an ideal voltage transformer, there should not be any phase difference between the primary voltage and the secondary voltage reversed. However, in an actual transformer, there exists a phase difference between Vo­ and V­s reversed.

The phase angle is taken as +ve when secondary voltage reversed leads to the primary voltage.

The angle is -ve when the secondary voltage reversed lags the primary voltage.

It can be reduced by keeping the primary and secondary windings are wound as closely as possible.

The phase angle error in current transformer is given as

\(\frac{180}{π} [\frac{I_m cosδ – I_c sinδ}{nI_s}]\) degrees

where

Im is the magnetizing component of the excitation current

Ic is the core loss component of the excitation current

Is is the secondary winding current.

 

46. To measure the current in a 1-ϕ transmission line, the primary winding of the current transformer is connected in:

  1. Series with the line carrying current
  2. Parallel to the load
  3. Parallel with the line carrying current
  4. Parallel to the source

Answer.1. Series with the line carrying current

Explanation:

The primary winding of the current transformer is connected in series with the transmission line whose current is to be measured.

If you try to connect a CT in parallel with another resistance or load, the coil of the CT will seem to offer negligible resistance or simply it will work as a short circuit.

The potential transformer is connected in parallel with the line.

 

47. Phase angle error in current transformer is given by _______

a) \(\frac{180}{π} [\frac{1}{nI_s}]\)

b) \(\frac{180}{π} [\frac{I_m}{I_s}]\)

c) \(\frac{180}{π} [\frac{I_m}{n}]\)

d) \(\frac{180}{π} [\frac{I_m}{nI_s}]\)

Answer.d. \(\frac{180}{π} [\frac{I_m}{nI_s}]\)

Explanation:

The phase angle error in current transformer is given as

\(\frac{180}{π} [\frac{I_m cosδ – I_c sinδ}{nI_s}]\) degrees

In practice, the CT burden is largely resistive with a small value of inductance, thus the second phase angle δ is positive and generally small. Thus, sin δ ≈ 0 and cos δ ≈ 1. Therefore, the equation can be approximated as

\(\frac{180}{π} [\frac{I_m}{nI_s}]\)

 

48. The primary of 200/1 A, 5 VA, 0.8 pf current transformer carries 100 A. The secondary current is 0.495 A. The ratio error of the CT is

  1. -1.0%
  2. -0.5%
  3. +0.5%
  4. +1.0%

Answer.1. -1.0%

Explanation:

Nominal ration Kn = 200/1 = 200 A

Actual transformation ratio

R = Ip/Is =  100/0.495 = 202.02

Ratio error = 200 -202.2/202.2 = 1%

 

49. Ratio error in current transformer is largely depend on _________

  1. Iron loss
  2. Frequency
  3. Magnetizing component
  4. Supply voltage

Answer.1. Iron loss

Explanation:

The ratio error is considered to be positive when the actual ratio of the CT is less than the nominal ratio, i.e., when the secondary current, for a given primary current, is high.

The ratio error in a C.T. is given by the relation

Ratio error = Kn – RR = n + IeIs
where

Ie is the iron loss component of the excitation current

n is the turns ratio.

 

50. Precautions are essential for ensuring that the secondary of a current transformer is not open-circuited when the primary circuit is carrying current. This is due to

  1. The dangerously high voltage developed across secondary
  2. The ferromagnetic core may develop residual magnetism
  3. The reflected impedance may prevent the flow of current to the primary circuit
  4. None of the above

Answer.1. Dangerously high voltage develop across secondary

Explanation:

The secondary side of the current transformer is always kept short-circuited in order to avoid core saturation and high voltage induction so that the current transformer can be used to measure high values of currents.

Scroll to Top