A transmission line of surge impedance 300Ω is connected to a load of 300Ω.

A transmission line of surge impedance 300Ω is connected to a load of 300Ω. The reflection coefficient of the transmission line at the load end will be

Right Answer is: 0

SOLUTION

Surge impedance = 300Ω

End line load = 300Ω

The reflection coefficient of the transmission line at the load end is given by

ρ = (ZL − Zo)/(ZL + Zo)

Where,

ZL = Load or termination impedance at the end of the line

Zo = Characteristics impedance or Surge impedance

ρ = (300 − 300)/(300 + 300)

ρ = 0